| Indoor |
FDU90KXE6F-W |
FDU112KXE6F-W |
FDU140KXE6F-W |
FDU160KXE6F-W |
FDU112KXE6F-W |
FDU140KXE6F-W |
FDU160KXE6F-W |
FDU224KXZE1 |
FDU280KXZE1 |
| Outdoor |
FDC90KXZEN1-W |
FDC112KXZEN1-W |
FDC140KXZEN1-W |
FDCA155KXZEN1-W |
FDC112KXZES1-W |
FDC140KXZES1-W |
FDCA155KXZES1-W |
FDC224KXZPE1 |
FDC280KXZPE1 |
| Power source (Outdoor Unit) |
|
|
1 Phase 240V 50Hz |
3 Phase 380-415V 50Hz |
*Operation
data |
Nominal Capacity (Range) |
Cooling T1 |
kW |
9 |
11.2 |
14 |
15.2 |
11.2 |
14 |
15.2 |
22.4 |
28 |
| Heating H1 |
9 |
11.2 |
14 |
15.5 |
11.2 |
14 |
15.5 |
22.4 |
28 |
| Power consumption |
Indoor |
Cooling T1 |
kW |
0.25 |
0.32 |
0.36 |
0.43 |
0.32 |
0.36 |
0.43 |
1.2 |
1.2 |
| Heating H1 |
0.25 |
0.32 |
0.36 |
0.43 |
0.32 |
0.36 |
0.43 |
1.2 |
1.2 |
| Outdoor |
Cooling T1 |
1.98 |
2.55 |
4 |
4.87 |
2.55 |
4 |
4.87 |
5.6 |
7.87 |
| Heating H1 |
1.93 |
2.53 |
3.52 |
4.06 |
2.53 |
3.52 |
4.06 |
4.8 |
6.47 |
Running
current |
Indoor |
Cooling T1 |
A |
1.7 |
2 |
2.2 |
2.5 |
2 |
2.2 |
2.5 |
6.5 |
6.5 |
| Heating H1 |
1.7 |
2 |
2.2 |
2.5 |
2 |
2.2 |
2.5 |
6.5 |
6.5 |
| Outdoor |
Cooling T1 |
8.3 |
10.7 |
16.8 |
20.5 |
3.8 |
6 |
7.4 |
9.2 |
12.9 |
| Heating H1 |
8.1 |
10.6 |
14.8 |
17.1 |
3.8 |
5.4 |
6.2 |
7.9 |
10.6 |
| Inrush current, maximum current |
A |
5, 23 |
5, 23 |
5, 23 |
5, 23 |
5, 13.5 |
5, 13.5 |
5, 13.5 |
5, 21 |
5, 22 |
| Sound pressure level (JIS C9612) |
Indoor |
dB (A) |
P-H:37 Hi:31
Me:27 Lo:22 |
P-Hi:40 Hi:36
Me:34 Lo:28 |
P-Hi:41 Hi:37
Me:34 Lo:28 |
P-Hi:45 Hi:38
Me:34 Lo:29 |
P-Hi:40 Hi:36
Me:34 Lo:28 |
P-Hi:41 Hi:37
Me:34 Lo:28 |
P-Hi:45 Hi:38
Me:34 Lo:29 |
P-Hi52 Hi:50
Me:47 Lo:45 |
P-Hi52 Hi:50
Me:47 Lo:45 |
| Outdoor |
53 |
54 |
54 |
54 |
54 |
54 |
54 |
60 |
63 |
| External dimensions (HxWxD) |
Indoor |
mm |
280 x 950 x 635 |
280 × 1368 × 740 |
280 × 1368 × 740 |
280 × 1368 × 740 |
280 × 1368 × 740 |
280 × 1368 × 740 |
280 × 1368 × 740 |
379 x 1600 x 893 |
379 x 1600 x 893 |
| Outdoor |
845 x 970 x 370 |
845x970x370 |
845x970x370 |
845x970x370 |
845x970x370 |
845x970x370 |
845x970x370 |
1505x970x370 |
1505x970x370 |
| Net weight |
Indoor |
kg |
34 |
54 |
54 |
54 |
54 |
54 |
54 |
89 |
89 |
| Outdoor |
85 |
85 |
85 |
85 |
87 |
87 |
87 |
165 |
165 |
| Supply air connection |
mm |
170 x 880 |
170 x 1200 |
170 x 1200 |
170 x 1200 |
170 x 1200 |
170 x 1200 |
170 x 1200 |
250 x 1450 |
250 x 1450 |
| Return air connection |
mm |
200 x 740 |
235 x 1280 |
235 x 1280 |
235 x 1280 |
235 x 1280 |
235 x 1280 |
235 x 1280 |
250 x 1450 |
250 x 1450 |
| External Static Pressure (max) |
Pa |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
| Airflow |
Indoor (Cooling) |
l/s |
P-Hi:400 Hi:317
Me:250 Lo:167 |
P-Hi:600 Hi:467
Me:417 Lo:317 |
P-Hi:650 Hi:533
Me:433 Lo:333 |
P-Hi:800 Hi:583
Me:467 Lo:367 |
P-Hi:600 Hi:467
Me:417 Lo:317 |
P-Hi:650 Hi:533
Me:433 Lo:333 |
P-Hi:800 Hi:583
Me:467 Lo:367 |
P-Hi:1333 Hi:1200
Me:1067 Lo:933 |
P-Hi:1333 Hi:1200
Me:1067 Lo:933 |
| Indoor (Heating) |
| Refrigerant (Type, amount, pre-charge length) |
Quantity |
kg |
(R32) 4.2 |
(R410A) 8.9 |
| Pre charged to pipe length |
m |
30*** |
30*** |
30*** |
30*** |
30*** |
30*** |
30*** |
0.5*** |
0.5*** |
Installation
data |
Refrigerant piping |
Liquid line |
mm |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
| Gas line |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø19.05 |
Ø22.22 |
| Connection method |
|
Flare Connection |
Liquid: Flare / Gas: Brazing |
| Maximum pipe (one way) length |
m |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
90 |
90 |
| Max vertical height diff. between O.U. and I.U. |
m |
30 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) |
30 ( O.U. above I.U. ) / 30 ( O.U. below I.U. ) |
| Controller |
|
RC-E5, RC-EXZ3A, RCH-E3 or RCN-KIT4-E2 |
| Motion Sensor (Optional) |
|
LB-KIT2 |
|
|
| Demand response (AS4755) |
No |
No |
No |
No |
No |
No |
No |
No |
No |
| Outdoor air temperature (upper, lower limits) |
Cooling |
C |
-15 to 43 |
-15 to 43 |
-15 to 43 |
-15 to 43 |
-15 to 43 |
-15 to 43 |
-15 to 43 |
-15 to 50 |
-15 to 50 |
| Heating |
C |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
| * Operation data has been gathered in accordance with AS/NZS 3823 standards. ** Maximum 70m(Gas piping:φ25.4 or φ28.58), Maximum 35m (Gas piping:φ22.22). *** Please refer to E-solution software or technical manual for additional refrigerent requirments |