Set |
FDU71AVNXWVH |
FDU100AVNAWVH |
FDU100AVNPWVH |
FDU125VNPWVH |
FDU125AVNPWVH |
FDU125AVNXWVH |
FDU140AVNXWVH |
FDU100AVSAWVH |
FDU125AVSXWVH |
FDU140AVSXWVH |
Indoor |
FDU71VH |
FDU100VH |
FDU100VH |
FDU125VH |
FDU125VH |
FDU125VH |
FDU140VH |
FDU100VH |
FDU125VH |
FDU140VH |
Outdoor |
FDCA71VNX-W |
FDCA100VNA-W |
FDCA100VNP-W |
FDC125VNP-W |
FDCA125VNP-W |
FDCA125VNX-W |
FDCA140VNX-W |
FDCA100VSA-W |
FDCA125VSX-W |
FDCA140VSX-W |
Power source (Outdoor Unit) |
|
1 Phase 240V 50Hz |
3 Phase 380-415V 50Hz |
*Operation
data |
Nominal Capacity (Range) |
Cooling T1 |
kW |
7.1 (3.2-8.0) |
10.0 (4.0-11.2) |
10 (2.1 -10.2) |
12.1 (5.0-12.1) |
12.1 (5.0-12.1) |
12.5 (3.5-14.0) |
14.0 (3.5-16.0) |
10.0 (4.0-11.2) |
12.5 (3.5-14.0) |
14.0 (3.5-16.0) |
Heating H1 |
8.0 (3.6-9.0) |
11.2 (4.0-12.5) |
10 (1.7 – 10.4) |
12.1 (4.0-13.3) |
12.1 (4.0-13.3) |
14.0 (2.7-17.0) |
16.0 (2.7-18.0) |
11.2 (4.0-12.5) |
14.0 (2.7-18.0) |
16.0 (2.7-20.0) |
Heating H2 |
7.4 |
10 |
7.6 |
7.9 |
7.9 |
13.1 |
15.5 |
10 |
13.1 |
15.5 |
Power consumption |
Cooling T1 |
kW |
1.77 |
2.99 |
3.08 |
3.85 |
3.85 |
3.49 |
4.22 |
2.99 |
3.49 |
4.22 |
Heating H1 |
1.78 |
2.66 |
2.45 |
3.28 |
3.28 |
3.61 |
4.22 |
2.66 |
3.61 |
4.22 |
Maximum power consumption |
kW |
4.11 |
6.4 |
4.46 |
4.75 |
4.75 |
7.1 |
7.1 |
10.2 |
8.9 |
8.9 |
Running current |
Cooling T1 |
A |
7.9 |
14.3 |
13.1 |
16.2 |
16.2 |
15.3 |
18.5 |
4.6 |
5.6 |
6.7 |
Heating H1 |
7.9 |
12.7 |
10.4 |
13.8 |
13.8 |
15.9 |
18.5 |
4.1 |
5.9 |
6.8 |
Inrush current, maximum current |
A |
5, 20 |
5, 26 |
5, 19 |
5, 20 |
5, 20 |
5, 28 |
5, 30 |
5, 17 |
5, 16 |
5, 17 |
EER |
Cooling T1 |
|
4.01 |
3.35 |
3.25 |
3.14 |
3.14 |
3.58 |
3.32 |
3.35 |
3.58 |
3.32 |
COP |
Heating H1 |
4.49 |
4.21 |
4.08 |
3.69 |
3.69 |
3.88 |
3.79 |
4.21 |
3.88 |
3.79 |
Sound power level
(JIS C9612) |
Outdoor |
dB(A) |
66 |
70 |
68 |
73 |
73 |
68 |
69 |
69 |
68 |
69 |
Sound pressure level
(JIS C9612) |
Indoor |
dB (A) |
P-Hi:38 Hi:33
Me:29 Lo:25 |
P-Hi:44 Hi:38
Me:36 Lo:30 |
P-Hi: 44 Hi: 38
Me: 36 Lo: 30 |
P-Hi:45 Hi:40
Me:34 Lo:29 |
P-Hi:45 Hi:40
Me:34 Lo:29 |
P-Hi:45 Hi:40
Me:34 Lo:29 |
P-Hi:47 Hi:40
Me:35 Lo:30 |
P-Hi:44 Hi:38
Me:36 Lo:30 |
P-Hi:45 Hi:40
Me:34 Lo:29 |
P-Hi:47 Hi:40
Me:35 Lo:30 |
Outdoor |
51 |
55 |
56 |
57 |
57 |
54 |
54 |
55 |
54 |
54 |
External dimensions (HxWxD) |
Indoor |
mm |
280x950x635 |
280×1370×740 |
280x1370x740 |
280×1370×740 |
280×1370×740 |
280×1370×740 |
280×1370×740 |
280×1370×740 |
280×1370×740 |
280×1370×740 |
Outdoor |
750×880(+88)x340 |
845x970x370 |
750 × 880(+88) × 340 |
845x970x370 |
845x970x370 |
1300x970x370 |
1300x970x370 |
845x970x370 |
1300x970x370 |
1300x970x370 |
Net weight |
Indoor |
kg |
34 |
54 |
54 |
54 |
54 |
54 |
54 |
54 |
54 |
54 |
Outdoor |
60 |
77 |
57 |
73 |
73 |
97 |
97 |
78 |
99 |
99 |
Supply air connection |
mm |
170×880 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
170×1200 |
Return air connection |
mm |
200×740 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
235×1280 |
External Static Pressure (max) |
Pa |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
Airflow |
Indoor (Cooling) |
l/s |
P-Hi: 400 Hi: 316
Me: 250 Lo: 166 |
P-Hi: 600 Hi: 467
Me: 417 Lo: 317 |
P-Hi:600 Hi:467 Me:417 Lo:317 |
P-Hi:650 Hi:533 Me:433 Lo:333 |
P-Hi:650 Hi:533 Me:433 Lo:333 |
P-Hi:650 Hi:533 Me:433 Lo:333 |
P-Hi:800 Hi:583 Me:467 Lo:367 |
P-Hi: 600 Hi: 467
Me: 417 Lo: 317 |
P-Hi:650 Hi:533 Me:433 Lo:333 |
P-Hi:800 Hi:583 Me:467 Lo:367 |
Indoor (Heating) |
Refrigerant (R32) |
Quantity |
kg |
2.75 |
3.3 |
1.7 |
2.25 |
2.25 |
4 |
4 |
3.3 |
4 |
4 |
Pre charged to pipe length |
m |
30 |
30 |
15 |
15 |
15 |
30 |
30 |
30 |
30 |
30 |
Installation data |
Refrigerant piping |
Liquid line |
mm |
Ø9.52 |
Ø9.52 |
Ø6.35** |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Ø9.52 |
Gas line |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Ø15.88 |
Connection method |
|
Flare Connection |
Flare Connection |
Maximum pipe (one way) length |
m |
50 |
50 |
30 |
30 |
30 |
100 |
100 |
50 |
100 |
100 |
Max vertical height diff. between O.U. and I.U. |
m |
30 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) |
50 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) |
20 ( O.U. above I.U. ) / 20 ( O.U. below I.U. ) |
20 ( O.U. above I.U. ) / 20 ( O.U. below I.U. ) |
20 ( O.U. above I.U. ) / 20 ( O.U. below I.U. ) |
50 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) |
50 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) |
Controller |
RC-E5, RC-EXZ3A, RCH-E3 or RCN-KIT4-E2 |
RC-E5, RC-EXZ3A, RCH-E3 or RCN-KIT4-E2 |
Motion Sensor (Optional) |
LB-KIT2 |
LB-KIT2 |
Demand response (AS4755) |
Yes |
Yes |
Yes |
No |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Outdoor air temperature (upper, lower limits) |
Cooling |
C |
-15 to 50 |
-15 to 50 |
-15 to 46 |
-15 to 46 |
-15 to 46 |
-15 to 50 |
-15 to 50 |
-15 to 50 |
-15 to 50 |
-15 to 50 |
Heating |
C |
-20 to 20 |
-20 to 20 |
-15 to 20 |
-15 to 20 |
-15 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
-20 to 20 |
* Operation data has been gathered in accordance with AS/NZS 3823 standards. |
**Reducer set Ø9.52 –> Ø6.35 is included in the outdoor unit as accessory for FDCA100VNP-W |